Devices > KT-300 Combus Modules
KT-300 Combus Modules

Five Combus modules can be connected to a KT-300:

•  KT-PC4108 (8-zone input expansion module). This module has a tamper contact input.

•  KT-PC4116 (16-zone input expansion module). This module has a tamper contact input.

•  KT-PC4204 (4-relay/power supply expansion module). It has a tamper contact input and also includes a built-in 12VDC, 1A power supply for field devices.

•  KT-PC4216 (16-zone output expansion module). It can be used for elevator control, although additional hardware may be required.

•  KT-LCD3 (Kantech 32-character liquid crystal display). The LCD is green (normal status), red (power failure) and yellow (trouble).

1 - If a Combus module is installed to the KT-300 controller, click the Combus module configuration button. Undefined Combus terminals are identified by red flags/bullets. Once a module has been defined, it is identified by a green flag.

2 - To define a module, select one, then click the Define button (lower part of the window). The Enter Combus module serial number message box appears.

3 - Enter the module’s serial number, then click OK.

Closed Note...

4 - Assign names to the modules in the language fields.

5 - Check the options related to the module you want to configure (if these are displayed in the window).

Closed Note...

The following table summarizes the options associated with each module:

Combus type Options Additional options
KT3-LCD Combus low power, display date and time No additional options
KT-PC4108 Tamper alarm, Combus low power 8-input module
KT-PC4116 Tamper alarm, Combus low power 16-input module
KT-PC4204 Tamper alarm, Combus low power, Low battery, Power failure, lower auxiliary power Used as relays (1-4)
KT-PC4216 Tamper alarm, Combus low power Used as outputs

6 - Check the Combus low power option so that the KT-300 will report any Combus low power condition.

7 - Check Display date and time option so that LCD can display the date and time.

8 - When you have finished configuring the Combus module, click the OK button to go back to the Status relay tab.

9 - Associate a Local activation relay for Power failure, Combus failure and Combus low power (multi-site Gateway only). If you want to assign a specific relay, you may click the three-dot button and select a specific relay or group of relays.

Closed Note...

10 - Under Priority call type, assign the call type option that best suits failure event reporting (multi-site Gateway only). To access the Priority call type feature, the site connection type must be set to Modem.

Closed Note...